Dispatcher MIMIC board conroller KSH-32

KSH-32 — MIMIC board controller

KSH-32 is an autonomous component part of SOIKP. 

Main task to convert IEC870-5-104 into SOIK protocol.

Brief technical characteristics of the device for adapting protocols for the exchange of teleinformation to be dispalyed at dispatcher MIMIC board (KSH-32)
1. Technical characteristics:
— made on the basis of a module from the ICOP family of industrial controllers;
— basic Linux operating system (v. 2.6.29);
— number of dedicated digital channels with RS-485 interface: 4 channels;
— Ethernet 10/100 Base – 1;

— duplex channels with RS-485 interfaces, for data exchange according to standard asynchronous protocols at speeds ranging from 9600 to 115,000 baud;
— design execution – plastic case with mounting on a DIN rail;
— overall dimensions 150x70x110 mm, complete with a mounting bar with fasteners for installation on a DIN rail;
— mechanical protection — IP20;
— External connections using:
a) to subordinate devices with synchronous exchange protocols and to 24 V power circuits — terminal disconnectors;
b) to the computer network – RJ-45 connector;
c) 4 dedicated digital channels with RS-485 interface — DB-9 connector;
— service LEDs are installed on the two side walls of the case, which reflect the presence of secondary power supply voltages and the operating status of both the device itself and the data exchange through the communication channels involved.

2. List of performed functions:

-Main function to convert IEC870-5-104 into SOIK protocol.

— has WEB SCADA on board with TLS encryption, support RC commands,  Setpoints, value substitution;

— service software for configuration according to the conditions on the KPLconfig object and the editor of web schemes WEBeditor.

-transparent COM port mode for all RS-485;

− cyclic polling of subordinate devices ;
— reception of DI , ME data, which are transmitted cyclically without polling;
— cyclic transfer of RC, ME data without requests;
− synchronization of own system clock by the control server NTP/SCADA;
— reception of RC commands from the SCADA server and their retransmission to the corresponding subordinate device;
— temporary archiving of operational information in case of loss of communication channel with the control server;
— issuance, at the request of the control server, of the full volume of information about the collected values of parameters of the vehicle, ME;
− setting of insensitivity zones for ME parameters;
− setting the parameters of ME information exchange channels;

−supports exchange using specialized protocols, such as:

  • Modbus RTU Serial (Master/Slave);
  • Modbus RTU TCP/IP (Master/Slave);
  • IEC60870-5-101 (Master/Slave);
  • IEC60870-5-103(Master/——-);
  • IEC60870-5-104 (Master/Slave);
  • IEC61850-8 MMS (Master/Slave);
  • DNP3.0 (Master/——-);

— in addition, supports exchange using specialized protocols, such as:

  • SPA (ABB company)
  • GPS time NMEA
  • NTP server/client
  • SNMP
  • PLC functions aka IEC 61131
  • 2GPIO channels
  • SOIKP
  • PO-3

− real-time data exchange support with subordinate devices;

— real-time support for data exchange with subordinate devices;
− control of communication parameters with a subordinate device, formation of service logic signals regarding the working status and quality of communication;
− update of configuration parameters and built-in software remotely via a network channel;

3. Operating characteristics:
— work in closed premises with a high level of danger;
− ambient temperature from -20 to +50 °C;
− supply voltage +24 V direct current, power consumption up to 8 W;
— warranty period of service 36 months;
— warranty period of 12 years.
Note. KPL-32 is a component of the MKSU product (TU U 31.2-25641912-001: 2011) and can be supplied as a separate device.

Made in Ukraine

An example of the implementation of the WEB interface of the KSH-32 controller. WEB schema dublicates MIMIC board.

An example of the implementation of the WEB interface of the KSH-32 controller. the scheme duplicates the display on the PCTS64 shield modules

An example of the implementation of the WEB interface of the KSH-32 controller. the scheme duplicates the display on the PCTS128 shield modules

Example of manual entry of DI (simulation)